hamburger-nav-icon
region-flag-icon
Search by Category
Audio
Cameras
Cases & Bags
Computers & Software
Conferencing
Content Management
Control
Displays
Furniture
Home Technology/Automation
Lighting & Studio
Mounts & Rigging
Networking & Cabling
Power
Presentation
Production & Lighting
Security & Safety
Signal Management
Search by Category
Flag
EnglishFrenchGermanItalianPortugueseSpanish
Network Technologies Inc. (NTI) - E-CD10-y
Network Technologies Inc. (NTI) - E-CD10-y Network Technologies Inc. (NTI) - E-CD10-y
Request Quote
network-technologies-nti

Chemical Detection Sensor, 10 feet Chemical Sensor Cable

Model: E-CD10-y

  • For detecting the presence of chemical liquid. Reliably senses acids, bases, and other conductive liquids.
  • Detects liquid depth >0.1" (2.5 mm).
  • Minimum puddle: 0.6" (15 mm) diameter.
  • Chemical resistant – cable functions normally after seven-day exposure to: Fresh deionized water Tap water Sulfuric acid (98%) Sulfuric acid (50%) Hydrochloric acid (37%) Sodium hydroxide (10%) Aqua regia Ethylene glycol (60% in DI water)
  • Features a non-conductive polymer mesh that prevents false alarms caused by dirt/dust buildup, metal contact, or pressure on the rope.
Compare
Project List
Product Info
Related Products
Accessories

Environment Monitoring System Rope-Style Leak Detection Sensors
Liquid, Water & Chemical Detection Sensors compatible with E-2D, E-5D, E-16D, E-1W, E-MINI-LXO and E-MICRO

Choose the right Water Sensor Cable and 2-Wire Cable Length and learn more here: http://www.networktechinc.com/rope-style-leak-detector.html

  • For detecting the presence of chemical liquid. Reliably senses acids, bases, and other conductive liquids.
  • Detects liquid depth >0.1" (2.5 mm).
  • Minimum puddle: 0.6" (15 mm) diameter.
  • Chemical resistant – cable functions normally after seven-day exposure to: Fresh deionized water Tap water Sulfuric acid (98%) Sulfuric acid (50%) Hydrochloric acid (37%) Sodium hydroxide (10%) Aqua regia Ethylene glycol (60% in DI water)
  • Features a non-conductive polymer mesh that prevents false alarms caused by dirt/dust buildup, metal contact, or pressure on the rope.
  • Voltage and current: Open Circuit: 5VDC max @ 1µA. Closed circuit: <300mV @ 10.7mA.
  • Available chemical sensor cable (x) lengths: 1/10/50/100 feet. 100% waterproof
  • Available 2-wire cable (y) lengths: 5/10/20/50/100 feet. Contact an NTI product consultant for cable lengths over 100 feet (30 meters) – supports up to 1,000 feet (305 meters).
  • Use self-adhesive clips (E-CLPxx-LD) to prevent sensor rope cable from shifing after installation
 
Request Quote